PLSTAmbulatory Care

Plaster Room

Standard Area18
Ceiling Height2700mm

Briefing

Description
The Plaster Room allows for the application of plaster or other splints and for the closed reduction of displaced fractures or dislocations under sedative or regional anaesthesia.
Hours of Operation
Up to 24 hours (dependent on unit operating hours)
Occupancy
1 patient; 1 visitor; up to 4 staff
Additional Considerations
~ Typically provided as a dedicated room for high volume services, otherwise, a generic Treatment Room may be used with the inclusion of a plaster trap and other specific plastering equipment. ~ The cast saw shall incorporate an integrated dust extraction system or the room shall have an independent dust extraction system suitably located to capture the dust at source. A room exhaust shall also be included to prevent dust from entering adjacent spaces. ~ The plaster trap shall be easily accessible for cleaning and maintenance.

Performance Requirements

HVAC

Air Conditioning (General)Ventilation (Exhaust)

Lighting

Colour Corrected

Electrical

Body Protected

Nurse Call

Buttons / Handset

Items

CodeDescriptionQtyPriorityCategoryComment
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to corridor side, extent dependent on movement of beds and mobile equipment in adjacent area; to be coordinated with corridor wall protection
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 1[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
DOHI-114.01DOOR: hinged, 1 1/2 leaves, 1400 clear opening, solid, standard vision panel1StandardInternal - Door 1[DWGL-033]