Back to Components
INTV-MHMental Health

Interview Room - Mental Health

Standard Area14
Ceiling Height2700mm

Briefing

Description
The Interview Room - Mental Health (may be referred to on projects as a Dialogue Room) provides the space and amenities for interviews, counselling, collaborative care planning and small support network discussions.
Hours of Operation
Up to 24 hours (dependent on unit operating hours)
Occupancy
up to 6 persons;
Additional Considerations
~ Requirements for the selection of suitable finishes, hardware, fixtures and fittings of a type manufactured and marketed as anti-ligature (including any weight limits for load release for certain fixtures) must be confirmed at project level based on service requirements, patient safety policies, local design guidance, risk assessments and confirmation of operational models. This includes the door, door hardware, joinery surfaces, joinery hardware, engineering services outlets and any ceiling mounted fixtures and services. All tamper proof and anti-ligature items must be installed in accordance with their manufacturer's instructions. Anti-ligature fittings may require a performance solution to be provided for the room to meet accessibility requirements. This must be considered and addressed at project level to meet applicable legislation and standards (to be confirmed with the project accessibility and building code consultants). ~All glazing (including external windows) is to be Grade A safety glass to comply with AS/NZS 2208 and AS 1288. Toughened and laminated glass with a structural interlayer is recommended. Additional requirements for glazing are to be confirmed at project level to suit the specific mental health environment (i.e. non-acute, acute, intensive care). ~ It is recommended that the door set is selected as a full assembly to ensure the leaf, frame and hardware are coordinated and meet all tamper proof, anti-ligature and anti-barricade requirements when used together. Inclusion and size of a vision panel to be confirmed to suit service requirements. Privacy film may be applied to the vision panel as required. ~ A second door is required for safety and security. The location of the second door will be dependent on the overall floor plan and availability of an appropriate area to egress. ~ Based on a risk assessment, ceiling height is to be confirmed at a project level in combination with considerations for FF&E selection to ensure consumers cannot reach or cause damage to the ceiling or services located on the ceiling. ~ Provision of a workstation is dependent on service requirements (e.g. for computer based assessments to be undertaken). Impact on furniture arrangement when workstation is included must be considered to support a positive dynamic between staff and consumers, and encourage participation of consumers as equal partners in care. ~ Consider the location of wi-fi access points to ensure strong coverage is provided for mobile duress functions. ~ Unique considerations for Intensive Care and Child and Adolescent areas are to be confirmed at project level to suit jurisdictional policies ~ The selection of finishes in rooms for mental health units is to be carefully considered to support the provision of a welcoming, warm and therapeutic atmosphere and should aim to eliminate an institutional feel. ~ Nearby access to a beverage bay or water fountain is recommended. ~ Natural light and external outlook is desirable. Consider placement of windows and room orientation to suit privacy requirements.

Performance Requirements

HVAC

Air Conditioning (General)

Lighting

GeneralDimmable

Electrical

Body Protected

Items

CodeDescriptionQtyPriorityCategoryComment
AFDFI-026DOOR GLAZING FINISH: vision panel, privacy film1StandardInternal - Door 1optional; as required to suit privacy requirements
AFDPR-001.01DOOR PROTECTION: kickplate, to 300H1StandardInternal - Door 1to room side
AFDPR-001.01DOOR PROTECTION: kickplate, to 300H1StandardInternal - Door 2to room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1OptionalInternal - Door 2to corridor side as required
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1to corridor side as required
AFDPR-056.01DOOR FRAME PROTECTION: full wrap, to 900H1OptionalInternal - Door 2optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AFDPR-056.01DOOR FRAME PROTECTION: full wrap, to 900H1OptionalInternal - Door 1optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AHWCV-001WINDOW COVERING: blind, roller, single1OptionalExternal - Window 1
DOHI-003.03DOOR: hinged, 1 leaf, 900 clear opening, solid, anti-ligature1StandardInternal - Door 2secondary egress
DOHI-013.08DOOR: hinged, 1 leaf, 900 clear opening, solid, anti-ligature, standard vision panel1StandardInternal - Door 1requirements for glazing in vision panel to be confirmed to suit the mental health environment
ITSE-261READER: security, access control, proximity card, wall mounted1StandardInternal - Door 1optional; provision to suit security and egress requirements
ITSE-261READER: security, access control, proximity card, wall mounted1StandardInternal - Door 2optional; provision to suit security and egress requirements
WIFX-156.01WINDOW: fixed, external, double glazed, sill at 750H1OptionalExternal - Window 1optional; natural light and external outlook is desirable; consider placement and room orientation for patient privacy; requirements for glazing to be confirmed to suit the mental health environment

Command Bar