Back to Components
CONS-UNAmbulatory Care

Consult Room - Universal Access

Standard Area17
Ceiling Height2700mm

Briefing

Description
The Consult Room - Universal Access will provide for private consultation and physical examination of a range of patients with or without support persons present.
Hours of Operation
Up to 24 hours (dependent on unit operating hours)
Occupancy
1 patient; 1-2 visitors; 1-2 staff
Additional Considerations
~ The spatial allowance will accommodate patients who (a) are using a wheelchair, including a bariatric sized wheelchair; or (b) require a hoist to transfer. ~ The position of the basin, dispensers and other fittings also allows for use by staff in wheelchairs. ~ A second door may be required for staff safety and security; the location of the second door will be dependent on the availability an appropriate area to egress. ~ It is anticipated that one of these rooms may be provided within a 'pod' of consult rooms. ~ An operational model for responding to calls from staff/patients will be needed to support the inclusion of a nurse call system and is to be determined based on service requirements.

Performance Requirements

HVAC

Air Conditioning (General)

Lighting

Colour Corrected

Electrical

Body Protected

Nurse Call

Buttons / Handset

Items

CodeDescriptionQtyPriorityCategoryComment
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1OptionalInternal - Door 2[DWPR-005] to room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to corridor side, extent dependent on movement of beds and mobile equipment in adjacent area; to be coordinated with corridor wall protection
AFDPR-006.01DOOR PROTECTION: plate, to 900H1OptionalInternal - Door 2[DWPR-005] to corridor side, extent dependent on movement of beds and mobile equipment in adjacent area; to be coordinated with corridor wall protection
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 2[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 1[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
DOHI-013.01DOOR: hinged, 1 leaf, 900 clear opening, solid, standard vision panel1OptionalInternal - Door 2[DWGL-005] optional, second door for egress
DOHI-114.01DOOR: hinged, 1 1/2 leaves, 1400 clear opening, solid, standard vision panel1StandardInternal - Door 1DWGL-033]