Back to Components
CLAB-ICardiac Investigations

Catheter Laboratory - Interventional

Standard Area55.5
Ceiling Height3000mm

Briefing

Description
A procedure room where interventional Cardiac Catheter procedures are undertaken in a controlled, clean environment and may include administration of sedation or, much less commonly, general anaesthesia.
Hours of Operation
Up to 24 hours (dependent on unit operating hours)
Occupancy
1 patient; up to 6 staff
Additional Considerations
~ A Control room will be located adjacent and may serve more than one procedure room. ~ A clinical scrub area should be located immediately adjacent to the room staff entry. ~ Radiation shielding as advised by Radiation Consultant. ~ A strut channel system able to carry moving loads may be required. ~ Cable ducts from Control Room and Equipment room will be required. ~ 'X-Ray in Use' lights are required outside each entry door. ~ Power to imaging equipment should be on emergency supply.

Performance Requirements

HVAC

Ventilation (Exhaust)Positive Pressure

Lighting

Colour Corrected

Electrical

Cardiac Protected

Nurse Call

Buttons / Handset

Items

CodeDescriptionQtyPriorityCategoryComment
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 2[DWPR-005] to control room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to procedure room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 2[DWPR-005] to procedure room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 3[DWPR-005] to sterile stock side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 3[DWPR-005] to procedure room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to corridor side, extent dependent on movement of beds and mobile equipment in adjacent area; to be coordinated with corridor wall protection
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 1[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 2[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1StandardInternal - Door 3[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
DOHI-013.07DOOR: hinged, 1 leaf, 900 clear opening, solid, shielded, standard vision panel, lead glass, with cover1StandardInternal - Door 3[DWGL-006] staff access to sterile stock/ scrub areas, with sliding cover for privacy
DOHI-013.07DOOR: hinged, 1 leaf, 900 clear opening, solid, shielded, standard vision panel, lead glass, with cover1StandardInternal - Door 2[DWGL-006] to control room
DOHI-204.02DOOR: hinged, 2 leaves, 1800 clear opening, solid, shielded1StandardInternal - Door 1[DWSC-034] to corridor
WIFX-007.03WINDOW: fixed, internal, single glazed, sill at 900H, shielded, lead glass1StandardInternal - Window 1[DWOB-009] to control room