Back to Components
CLAB-EPCardiac Investigations

Catheter Laboratory - Electrophysiology Studies

Standard Area60
Ceiling Height3000mm

Briefing

Description
A highly specialised procedure room where interventional Cardiac Catheter procedures are undertaken in an aseptic environment and may include administration of sedation or general anaesthesia.
Hours of Operation
Up to 24 hours (dependent on unit operating hours)
Occupancy
1 patient; up to 6 staff
Additional Considerations
~ The Catheter Laboratory - Electrophysiology Studies may also be used for electrophysiology (EP) studies and treatment and is typically only provided in hospitals of tertiary level or higher, where required. ~ A Control room will be located adjacent and may serve more than one procedure room. ~ A clinical scrub area should be located immediately adjacent to the room staff entry. ~ Radiation shielding as advised by Radiation Consultant. ~ A strut channel system able to carry moving loads may be required. ~ Cable ducts from Control Room and Equipment room will be required. ~ 'X-Ray in Use' lights are required outside each entry door. ~ Power to imaging equipment should be on emergency supply. ~ The Catheter Laboratory for EP studies will require radiofrequency shielding.

Performance Requirements

HVAC

Ventilation (Exhaust)Positive Pressure

Lighting

DimmableColour Corrected

Electrical

Cardiac Protected

Nurse Call

Buttons / Handset

Items

CodeDescriptionQtyPriorityCategoryComment
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to procedure room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 1[DWPR-005] to corridor side, extent dependent on movement of beds and mobile equipment in adjacent area; to be coordinated with corridor wall protection
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 2[DWPR-005] to control room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 3[DWPR-005] to procedure room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 2[DWPR-005] to procedure room side
AFDPR-006.01DOOR PROTECTION: plate, to 900H1StandardInternal - Door 3[DWPR-005] to sterile stock side
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1StandardInternal - Door 3[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 2[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
AFDPR-056.03DOOR FRAME PROTECTION: full wrap, to 1200H1OptionalInternal - Door 1[DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area
DOHI-013.07DOOR: hinged, 1 leaf, 900 clear opening, solid, shielded, standard vision panel, lead glass, with cover1StandardInternal - Door 2[DWGL-006] to control room
DOHI-013.07DOOR: hinged, 1 leaf, 900 clear opening, solid, shielded, standard vision panel, lead glass, with cover1StandardInternal - Door 3[DWGL-006] staff access to sterile stock/ scrub areas, with sliding cover for privacy
DOHI-204.02DOOR: hinged, 2 leaves, 1800 clear opening, solid, shielded1StandardInternal - Door 1[DWSC-034] to corridor
WIFX-007.03WINDOW: fixed, internal, single glazed, sill at 900H, shielded, lead glass1StandardInternal - Window 1[DWOB-009] to control room

Command Bar