ANTEInpatient Accommodation
Anteroom
Standard Area6m²
Ceiling Height2700mm
Briefing
Performance Requirements
HVAC
Air Conditioning (General)Ventilation (Exhaust)
Lighting
General
Electrical
Body Protected
Items
| Code | Description | Qty | Priority | Category | Comment |
|---|---|---|---|---|---|
| AFDPR-006.01 | DOOR PROTECTION: plate, to 900H | 1 | Standard | Internal - Door 1 | to corridor |
| AFDPR-006.01 | DOOR PROTECTION: plate, to 900H | 1 | Standard | Internal - Door 2 | to bedroom |
| AFDPR-056.01 | DOOR FRAME PROTECTION: full wrap, to 900H | 1 | Standard | Internal - Door 1 | [DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area |
| AFDPR-056.01 | DOOR FRAME PROTECTION: full wrap, to 900H | 1 | Standard | Internal - Door 2 | [DWPR-010] optional, provision and extent dependent on frame material/finish and movement of beds and mobile equipment in adjacent area |
| AHDEC-111 | DOOR CONTROL: connection, interlocking system | 1 | Standard | Internal - Door 2 | to ensure door is closed before the door to the corridor is opened and vice versa |
| AHDEC-111 | DOOR CONTROL: connection, interlocking system | 1 | Standard | Internal - Door 1 | to ensure door is closed before the door to the bedroom is opened and vice versa |
| DOHI-043.01 | DOOR: hinged, 1 leaf, 900 clear opening, solid, wide vision panel | 1 | Standard | Internal - Door 1 | — |
| DOHI-043.01 | DOOR: hinged, 1 leaf, 900 clear opening, solid, wide vision panel | 1 | Standard | Internal - Door 2 | — |
| ITSE-301 | ALARM: door release, emergency, break glass, wall mounted | 1 | Standard | Internal - Door 1 | for override of interlock system and release of corridor door to mitigate risk of staff entrapment |