ANAESOperating
Anaesthetic Preparation Room
Standard Area16m²
Ceiling Height2700mm
Briefing
Performance Requirements
HVAC
HEPA FilteredVentilation (Exhaust)Positive Pressure
Lighting
DimmableColour Corrected
Electrical
Body Protected
Nurse Call
Buttons / Handset
Items
| Code | Description | Qty | Priority | Category | Comment |
|---|---|---|---|---|---|
| AFDPR-006.01 | DOOR PROTECTION: plate, to 900H | 1 | Standard | Internal - Door 2 | — |
| AFDPR-006.05 | DOOR PROTECTION: plate, full height | 1 | Standard | Internal - Door 1 | to both sides |
| AHDEC-036 | SWITCH: door release, double gang, automatic door, wall mounted | 1 | Standard | Internal - Door 1 | to allow for opening either one or both leaves of the door |
| AHDMO-002 | DOOR MOTORISATION: hinged, 2 leaf | 1 | Standard | Internal - Door 1 | delayed action closing |
| DOHI-212.03 | DOOR: hinged, 2 leaves, 1600 clear opening, solid, standard vision panel, with cover | 1 | Standard | Internal - Door 1 | to operating room (see OR-GEN), cover required to vision panel if laser is to be used |
| DOSL-212.01 | DOOR: sliding, bi-parting, 2 leaves, 1600 clear opening, solid, standard vision panel | 1 | Standard | Internal - Door 2 | to corridor |